Engine OperationsEvolution 1.4

Official evolution · ADO-Pumper Task Book · September 2024

Evolution 1.4 — Place the deck gun in service while flowing additional hand lines

OBJECTIVE: Flow deck gun for quick knock down on simulated fire then transition to Hydrant supply with additional hand lines.

What the printed sheet says about this drill

The deck gun is a master stream device, so the master-stream order and the confirm-all-out stop below apply to it exactly as they do to a portable monitor or a ladder pipe (Engine Company Operations 2023 V-1, p.133 / 7-1).

In-cab operations

1

Right foot on brake

2

Set parking brake

3

Shift transmission to neutral

4

Shift from road to pump (engage the pump shift control lever)

5

Pump engaged light is on

6

Shift transmission to Drive (D)

7

OK TO PUMP light is on and

“and” is underlined on the printed sheet — the light alone is not the proof. Step 7a is the other half of it.

7a

Speedometer registers about 15 mph

The speedometer reading confirms the road-to-pump shift completed.

Orem rigs: Engine 34 only — pump shift operations
1

Right foot on brake

2

Neutral

3

Park brake

4

Engage “water pump” switch

5

Green light indicator on

8

Emergency/warning lights are on

9

Change radio to correct channel

10

Remove right foot from brake

11

Apparatus does not move

12

Exit cab after looking both directions

Out-of-cab operations — steps 1–6

Starting condition on the printed sheet: apparatus can be connected to a hydrant with all connections made. Intake is not open.
1

Verify pump is engaged

2

Open Tank to Pump

3

Crack re-circulating/tank fill valve

4

Set to PSI mode (if equipped)

5

Prime Pump (if necessary)

6

Set wheel chocks

Why & source
“Position the apparatus in a safe position, and immobilize it by setting the parking brake and chocking the wheels.”

Step 1 of the changeover procedure — the rig is immobilised before any water moves, and it stays chocked through the transition to hydrant supply.

ADO Task #19, Basic Pump Skills — Changeover, Operating Procedure Step 1

MASTER STREAM — the deck gun

The deck gun is a master stream device, so it gets the master-stream order from Engine Evolution: secure the device, calculate PDP, set PDP, notify Command big water is ready, confirm everyone is out, then open the discharge. On the task book sheet the opening action is out-of-cab step 7 — charge and flow water from Deck gun.
1

PROPERLY SECURE DEVICE

from Engine Evolution
Why & source

Higher flows are more likely to knock debris loose from the building and send it flying to strike people or apparatus. A deck gun mounted on the apparatus also has a limiter pin that prevents the nozzle being rotated too low.

Engine Company Operations 2023 V-1, pp.133–134 (7-1–7-2)

2

CALCULATE PDP

from Engine Evolution
The formula

PDP = F + E + A + N. Repeat F for every additional line or hose segment in the layout. E is elevation, A is appliance loss, N is nozzle pressure and it is counted exactly once. Start at the nozzle and work back to the pump.

OFD Hydraulic Manual §2.a and §2.c, as ruled 2026-08-29

3

SET PDP

from Engine Evolution
4

NOTIFY COMMAND BIG WATER IS READY

from Engine Evolution

STOP

Confirm all department members are out of the building before flowing the deck gun.

Affirmative acknowledgement, not a one-way notification. A master stream must be shut down to be repositioned, so the first placement has to be right — the safest exterior positions are the building corners; the front is dangerous, ineffective, and inside the collapse zone.

Engine Company Operations 2023 V-1, p.133 (7-1)
5

OPEN DISCHARGE

from Engine Evolution

On the task book sheet this is out-of-cab step 7 below.

Out-of-cab operations — steps 7–16, transition to hydrant supply

7

Charge and flow water from Deck gun

8

Set discharge to the right pressure

+

SET DISCHARGE RELIEF VALVE TO ~150

from Engine Evolution
Why
“…then when I introduce hydrant water there isn’t as much of a pressure spike and the discharge relief valve will catch any extra. Then after hydrant is fully opened I can throttle back down.”

Jason, 2026-08-30

+

THROTTLE UP TO 150 PSI

from Engine Evolution
+

GATE DOWN HANDLINES TO THEIR SET PDP

from Engine Evolution
9

Open intake from hydrant slowly, make sure Pressure governor adjusts pump pressure or manually adjust pressure if needed.

Why & source
“To begin the transition, the operator opens the intake valve from the supply line very slowly while observing the pressure on the intake and discharge gauges. Start opening intake valve and adjusting the discharge pressure until the intake is completely open. It may be necessary to adjust the engine throttle to get the desired discharge pressure.”

ADO Task #19, Basic Pump Skills — Changeover

+

THROTTLE BACK DOWN (ONCE HYDRANT IS FULLY OPEN)

from Engine Evolution
10

Verbalize supply is established

11

Close intake bleeder valve and tank to pump

Why & source
“Air in the empty supply hose will cause problems if it enters the pump while the pump is supplying attack lines under pressure. To purge this air, open the bleeder valve on the gated intake line so that the air can escape as the supply line fills with water. When all the air has been forced from the line, close the bleeder valve.”

The tank-fill valve is a different valve and does not close here — leave it partially open until the tank has refilled. A full tank is the reserve if the external supply is lost.

ADO Task #19, Basic Pump Skills — Changeover

12

Must be in PSI mode (for engines with pressure governors)

13

Break 2.5” handline if needed and charge to correct pressure

Pressures for the 2½” line

Orem’s smooth bore flows for the 2½”: 15/16” = 185 gpm at 50 psi nozzle pressure and 1⅛” = 265 gpm at 50 psi. Nozzle pressure enters the PDP once; the rest is friction loss, elevation and appliance loss.

OFD figures as ruled 2026-08-29 (supersedes the 180 / 250 estimating pair)

14

Mark or note discharge gauge & line length/location.

15

Check discharge pressures and adjust if needed

16

Set manual discharge relief valve

Manual valve: Engine 31 · Engine 3820 · Ladder 32

What the manual teaches — the deck gun & master streams

What counts as a master stream

The majority of structure fires an engine company meets can be handled with hand lines. On some occasions there is a fire that cannot be controlled by hand lines and requires the engine company to deliver large quantities of water from a great distance.

By most definitions, any stream greater than 350 gpm that requires mechanical assistance for handling is a “master” stream — also called large-caliber streams (LCS). They may be portable (“ground-based”), elevated (ladder pipes and nozzles on elevating platforms), or mounted atop the engine apparatus itself — which is what the deck gun is. They are deployed in situations, usually defensive, where the fire is beyond the ability of hand lines to control, or where a fire stream is needed in a location no longer safe for department members.

Engine Company Operations 2023 V-1, p.133 (7-1)

Everyone backed out first — the stop above

Master stream operations require a coordinated effort from the companies operating on scene, one of which is ensuring that all department members have been backed out of the building prior to flowing any master stream or elevated ladder pipe. That is the STOP above, and it is not specific to the ladder pipe — the deck gun is covered by the same sentence.

Engine Company Operations 2023 V-1, p.133 (7-1)

Safety — debris and a limited arc
  • There is an increased likelihood that the higher flows will knock debris loose from the building, sending it through the air to strike people or apparatus.
  • Operating in the portable mode, the master stream has a limited side-to-side range. Turning the nozzle too far left or right may cause the base to become unstable and tip over.

Engine Company Operations 2023 V-1, p.133 (7-1)

Positioning — corners, never the front

When master streams are placed into service it generally means interior offensive operations have been abandoned and a defensive posture is being employed. The device must be properly positioned to provide an effective stream: once the line is in operation, it must be shut down to be repositioned.

The safest exterior positions are at the corners of the building. Setting a master stream up in front of the building — whether operated from the top of the engine or from the ground — is a dangerous and ineffective tactic: the firefighters operating the stream are in the collapse zone and may not have enough time to react to a sudden collapse of an exterior wall.

Should a master stream have to operate from the front, it should be set back far enough that it will not be struck by falling walls or debris. The widely accepted figure is a collapse zone of one and one-half times the height of the tallest exterior wall — a store front with a 20-foot wall gets a 30-foot collapse safety zone, and the further the better.

Engine Company Operations 2023 V-1, pp.133–134 (7-1–7-2)

The deck gun’s one big drawback — height

A drawback with deck gun nozzles that sit as much as nine to ten feet above the ground is a dramatic loss of effectiveness at low-angle operations. Take the positioning limits imposed by a narrow street, combine them with the height of the deck gun above the ground, and most of the water is wasted — the stream hits the floor only 25 to 30 feet inside the structure.

A limiter pin prevents the nozzle from being rotated too low.

Engine Company Operations 2023 V-1, p.134 (7-2)

How the deck gun is used well — the quick knock down

The most effective operation in the use of the pre-connected deck gun is to direct a quick application of high-pressure water through the window to knock down the heavy fire while other members get a hand line into position by whatever means available. Faster fire control means increased life safety for civilians and firefighters. That is the objective of this evolution, in the manual’s own words.

At upper-floor operations the stream angle reduces the chance of “pushing” the fire through the compartment and out into the hallway: most of the water strikes the ceiling of the fire compartment and coarse droplets rain down on the burning contents. The penetration of deck gun streams decreases as the stream angle increases.

Employing a smaller tip than normally used with a deck gun, and limiting the application of water, further reduces the danger of forcing fire out of the compartment of origin. A 1½-inch tip is used to generate the high-velocity pressure necessary for reach and to conserve water.

Engine Company Operations 2023 V-1, p.135 (7-3)

The Stinger — deck gun or portable monitor

The Stinger is a dual-purpose break-apart monitor that can be used as a deck gun or as a portable monitor. It is mounted to a plumbed outlet on top of the engine with the nozzle assembly attached; because it is plumbed it can be placed into operation rapidly without having to run a supply line to it. Based on the tip in use, the Stinger can deliver up to 1,250 gallons per minute.

A disadvantage of using the Stinger in the deck-gun configuration: it may require the engine to be parked in close proximity to ensure proper reach, placing the apparatus in a potentially dangerous position.

Engine Company Operations 2023 V-1, p.136 (7-4)

Components — nozzle assembly and base

The two components that make up the monitor are the nozzle and the base. The nozzle is typically a combination fog nozzle, or a stacked set of smooth bore tips varying in size and gpm delivery — which is what the drill setup means by “utilize different smooth bore tip sizes.”

The nozzle assembly is the upper portion of the deck gun. Either a combination nozzle or a stacked tip set attaches to the nozzle assembly pipe. The assembly also carries a hand wheel for adjusting the angle of the tip and an in-line pressure gauge, and it can be affixed to either the engine or the portable base.

The base is a lightweight portable stand with folding legs for stability and a single 5” LDH inlet. Normally stored in the rear compartment, it can be set up at any desired location, removing the dangers of the fire from the apparatus and from firefighters working nearby. To use it: set up the base, remove the Stinger from the engine, and stretch the LDH supply line.

Engine Company Operations 2023 V-1, pp.136–137 (7-4–7-5)

Feeding it — what the supply has to carry

This evolution asks the hydrant to carry the deck gun and then a 2½” hand line as well. Two operative water-supply figures:

  • A double 2½” hydrant — two 2½” outlets on a 4” main with no steamer — should be expected to give less than 600 gpm.
  • Provide one 5” supply line per 1,000 gpm to be delivered.

The manual’s own reason for reaching for a smaller deck gun tip is reach and conserving water (p.135 / 7-3), not a supply calculation — but a Stinger that can take up to 1,250 gpm and a hydrant expected to give less than 600 are numbers worth having in your head before you open the discharge.

Double 2½” hydrant flow: Engine Company Operations 2023 V-1, p.100 (5-4). The one-5”-line-per-1,000-gpm figure is published per the 2026-08-29 ruling on chapter 5’s flow list; the remaining bullets in that p.101 (5-5) list are a known error in the manual and are not published here.

The changeover itself — ADO Task #19

Transition from the water tank to an external supply most commonly involves a pressurized source: a hose line supplied by another apparatus, or a fire hydrant.

  • Purge the air first. Air in the empty supply hose causes problems if it enters the pump while the pump is supplying attack lines under pressure. Open the bleeder valve on the gated intake so air escapes as the line fills; close it when all the air is out. The water is then at the pump and ready for the transition.
  • Open slowly, watching both gauges. Open the intake valve from the supply line very slowly while observing intake and discharge pressure, adjusting discharge pressure as you go until the intake is completely open. It may be necessary to adjust the engine throttle to get the desired discharge pressure.
  • Then close tank-to-pump. After the intake valve is open, the tank-to-pump valve can be closed — but the tank-fill valve should be left partially open until the tank has refilled. A full tank is a limited reserve if the external supply is lost unexpectedly.

ADO Task #19, Basic Pump Skills — Changeover (Transition to an External Water Supply)

Sources. ADO-Pumper Task Book, Evolution 1.4 (September 2024 version) — objective, setup, in-cab and out-of-cab steps verbatim with the printed numbering. Steps marked “+” and the master-stream order are merged in from Engine Evolution per my 2026-08-30 review. Manual material: Engine Company Operations 2023 V-1, Chapter 7 — Master Stream Operations (pp.133–137) and Chapter 5 — Water Supply (p.100); ADO Task #19, Basic Pump Skills — Changeover; OFD Hydraulic Manual for the PDP formula and the 2½” smooth bore flows.

Version: prototype · Last reviewed 2026-08-30 · Compiled by Engineer Jason Anderson

Sections