Engine OperationsEvolution 1.6

Official evolution · ADO-Pumper Task Book · September 2024

Evolution 1.6 — Utilize a standpipe to charge lines on a multi-story structure

Objective: Supply water to the 2.5″ initial attack line on a multi-story building through the standpipe system.

In-Cab Operations

1

Right foot on brake

2

Set parking brake

3

Shift transmission to neutral

4

Shift from road to pump (engage the pump shift control lever)

5

Pump engaged light is on

6

Shift transmission to Drive (D)

7

OK TO PUMP light is on

7a

Speedometer registers about 15 mph

Orem rigs: Engine 34 only

Engine 34 pump shift operations — on Engine 34 the pump shift runs this sub-sequence instead of the lever shift above. Printed on the task-book sheet as its own five-step block.

1

Right foot on brake

2

Neutral

3

Park brake

4

Engage “water pump” switch

5

Green light indicator on

8

Emergency/warning lights are on

9

Change radio to correct channel

10

Remove right foot from brake

11

Apparatus does not move

12

Exit cab after looking both directions

Out-Of-Cab Operations

1

Verify pump is engaged

2

Open Tank to Pump

3

Crack re-circulating/tank fill valve

4

Set to PSI mode

PSI/RPM mode: Engine 34 only

PSI/RPM button mode is a Pierce PUC control. At Orem that is Engine 34 — the other pumps have no PSI mode, so on those rigs the pressure is set at the pressure governor instead. The task book’s PSI mode and the changeover task’s transfer valve are two different controls, not two names for one action.

Engineer Jason Anderson, 2026-08-29 — rig-specific controls ruling.

5

Prime Pump (if necessary)

6

Set wheel chocks

Why & source
“Position the apparatus in a safe positon, and immobilize it by setting the parking brake and chocking the wheels.”

Evolution 1.6 prints the chock step. Some other evolution sheets omit it; where they do, the step is added to match this one.

ADO Task #19 Basic Pump Skills-Changeover — Operating Procedure, Step 1

7

Attach one 3″ supply hose to building standpipe system

Why 3″
“3″ hose should be used to supply all standpipe systems.”

Engine Company Operations 2023 V-1, 6-16 — Supplying Standpipe Systems

8

Break line and attach to Engine discharge port

9

Introduce hydrant and verbalize water supply established

OPEN SUPPLY INTAKE SLOWLY (MONITOR GAUGES)

Opening the intake — bleeder first, then very slowly
“Air in the empty supply hose will cause problems if it enters the pump while the pump is supplying attack lines under pressure. To purge this air, open the bleeder valve on the gated intake line so that the air can escape as the supply line fills with water. When all the air has been forced from the line, close the bleeder valve.”
“To begin the transition, the operator opens the intake valve from the supply line very slowly while observing the pressure on the intake and discharge gauges. Start opening intake valve and adjusting the discharge pressure until the intake is completely open.”

ADO Task #19 Basic Pump Skills-Changeover — Transition to an External Water Supply. The step above is from Engineer Jason Anderson’s engine evolution.

Relief-valve pre-set before hydrant water
“Set the Discharge Relief Valve to about 150, rev up psi to 150 while gating down the handlines to make sure they stay at the set pdp for them. then when i introduce hydrant water there isnt as much of a pressure spike and the discharge relief valve will catch any extra. then after hydrant is fully opened i can throttle back down.”

Engineer Jason Anderson, 2026-08-30 — the full sequence lives in Engine Evolution, Establish supply

10

Close the tank to pump valve

Leave the tank fill open until the tank is back
“After the intake valve is opened, the tank-to-pump valve can be closed. However, the (tank-fill) valve should be left partially open until the water tank has been refilled. Note: A full tank provides a limited reserve water supply in the event that the external water supply is lost unexpectedly.”

The re-circulating/tank fill valve cracked at out-of-cab step 3 does this job once hydrant water is in. The printed 1.6 sheet carries no separate refill step — the tank comes back through step 3.

ADO Task #19 Basic Pump Skills-Changeover — Transition to an External Water Supply

11

Mark or note intake gauge

*NOTE STATIC HYDRANT PRESSURE*

Why note it

USE 1ST DIGIT METHOD TO DETERMINE ADDITIONAL LIKE VOLUMES REMAINING.

Engineer Jason Anderson’s engine evolution — see My Engine Evolution

12

Charge standpipe system to correct PDP. (FL+Elevation+Appliance+NP)

Elevation — to the nozzle floor
“Wherever the nozzle is. 5 psi per floor.”

Elevation is calculated to the floor the nozzle is on, not the hookup floor: 5 psi per floor, minus the first floor. Applying the sheet’s own rule to its drills — third floor: 5 × (3−1) = 10 psi. Fourth floor: 5 × (4−1) = 15 psi.

Engineer Jason Anderson, 2026-08-30 · elevation rule as printed on the Evolution 1.6 setup. On a standpipe with a known pressure reducing valve the elevation term is based on the total height of the standpipe instead — OFD Hydraulic Manual, appliance loss §2.c.

Appliance — 25 psi for the standpipe

The printed setup allows 25 psi appliance loss for the standpipe. It sits in the PDP alongside friction loss in all the hose, elevation, and nozzle pressure.

ADO-Pumper Task Book, Evolution 1.6 setup — September 2024

The whole calculation — friction loss numbers, both drills worked out end to end — is in what the manual teaches, below.

13

Stretch second 3″ standpipe supply line

Why a second line
“It is important to provide an independent and a redundant water supply… This ensures that firefighters advancing hoselines will have an uninterrupted supply of water should a pumper suffer a mechanical failure or the FDC supplies only a single stairwell riser.”

Engine Company Operations 2023 V-1, 6-16 — Supplying Standpipe Systems

14

Adjust pressure is needed.

As printed on the task-book sheet.

15

Set manual discharge relief valve

Manual valve: Engine 31 · Engine 3820 · Ladder 32

Printed last on the sheet. The changeover task sets it earlier — before pressure is put to the line, not after — which is why the pre-set sits at step 9 above.

Where the changeover task puts it
“Step 5: Increase the throttle setting to obtain the desired pressure, priming (if necessary). Step 6: Set the relief valve or pressure governor. Step 7: Open the circulator valve or partially open the tank fill valve. Step 8: When an external supply becomes available, open the intake valve while closing the tank-to-pump valve…”

ADO Task #19 Basic Pump Skills-Changeover — Operating Procedure, Steps 5–8

20

Maintain 20 PSI intake pressure

20 psi minimum protects from drawing a vacuum on the intake hose. — Engineer Jason Anderson’s engine evolution.

WHAT THE MANUAL TEACHES ABOUT STANDPIPES

What Engine Company Operations Chapter 6 and the OFD Hydraulic Manual say about the system you are pumping into, and about the pressure you owe it. Open what you need.

The pressure you owe the standpipe — F + E + A + N

PDP = F + E + A + N. Start at the nozzle and work back to the pump. F repeats for every additional line or hose segment in the layout; N is counted exactly once — nozzle pressure is a component of PDP, not a component of friction loss.

  • F — friction loss. Standard per 100′: 2½″ at 265 GPM = 16 psi by the field method (14 psi by C·Q²·L); 3″ at 300 GPM = 9 psi field (7.2 by C·Q²·L). Coefficients: 2½″ = 2, 3″ = 0.8. Field method for 2½″ in the 100–300 GPM range: take the first two digits of the GPM and subtract 10 (265 → 26 − 10 = 16).
  • E — elevation. Structural: 5 psi per floor, minus the first floor. Computed to the floor the nozzle is on, not the hookup floor. A sub-level is a gain and is subtracted. Exception: on a standpipe with a known pressure reducing valve, elevation is based on the total height of the standpipe.
  • A — appliance. The standpipe is a large appliance: 25 psi regardless of flow. That is the same 25 psi the printed 1.6 setup allows.
  • N — nozzle pressure. The 1⅛″ smooth bore in the high-rise shut-off flows 265 GPM at 50 psi — the flow both 1.6 drills are written to.

Do not carry the 150 over. The 150 psi pumped into a sprinkler FDC is its own rule, outside this math. A standpipe is calculated normally, with its own 25 psi appliance allowance.

OFD Hydraulic Manual — Calculating Pump Discharge Pressure §2 (FL / EL / AL), Friction Loss Standard per 100′ table, hose coefficient table, smooth-bore tip table · Engine Company Operations 2023 V-1, 6-6 (high-rise nozzle) and 6-14 (1⅛″ at 50 psi nozzle pressure). Nozzle pressure counted once, and elevation computed to the nozzle floor, per Engineer Jason Anderson’s 2026-08-29 and 2026-08-30 rulings.

The two printed drills, worked out

Every figure below is either printed on the 1.6 sheet or comes from the manual numbers in the block above. Nothing is estimated.

Term Drill 1 — 3rd floor
150′ of 2½″, 265 GPM
Drill 2 — 4th floor
200′ of 2½″, 265 GPM
F — attack line16 × 1.5 = 24 psi16 × 2 = 32 psi
E — elevation to the nozzle floor5 × (3−1) = 10 psi5 × (4−1) = 15 psi
A — standpipe25 psi25 psi
N — 1⅛″ smooth bore50 psi50 psi
Pressure the standpipe needs109 psi122 psi

Then add the friction loss in your own supply lines. The sheet does not give a length for the two 3″ lines from the pump to the building connection, so that F term comes from the lay you actually made. The totals above are what has to arrive at the standpipe.

If the building has a known pressure reducing valve, the elevation term is not 5 psi per fire floor — it is based on the total height of the standpipe.

Drill figures: ADO-Pumper Task Book, Evolution 1.6 setup, September 2024 · pressures: OFD Hydraulic Manual as cited above.

Standpipe assignments — whose job this evolution is

This evolution is the second arriving Engine’s work on a first alarm. The manual’s assignment sheet gives the engineer the task by name:

“The Engineer shall establish the initial standpipe system and/or support a combination system with primary connections. After securing a water supply, the Engineer should proceed to the standpipe and/or combination system connection, make the connections, and begin pumping operations.”

The rest of that crew is not standing by: the Back-up, Tailboard and Nozzle Firefighters assist the engineer with the water supply and the standpipe connections before the Back-up and Nozzle Firefighters go up with packs and tools. All equipment from the second engine is placed outside the stairwell two floors below the fire, and the company then assists the first engine with advancing the first line.

On the first engine the engineer does not stay at the pump panel — that engineer takes the high-rise bag and pack and goes with the company to the standpipe outlet one floor below the fire floor. Which is why the standpipe gets pumped by the second engine.

The Quick Response Guide gives the same second-engine function: “Establish water supply, Pump standpipe if 1st Engine determines standpipe operations.”

Engine Company Operations 2023 V-1, 6-11 to 6-12 — Standpipe Assignments · OFD Quick Reference Guide (May 2024), 2nd Engine Company Functions

Wet, dry, and the three classes

Standpipe systems are categorized by outlet size and as wet or dry. Wet systems hold water in the riser at all times, supplied by municipal main, gravity tank, pressure tank, or a combination — often with fire pumps boosting pressure to the upper floors. Dry systems have no automatic source of supply and depend solely on fire department pumpers to provide the system demand. On a dry standpipe, “fire department pumpers provide the only water supply available for firefighting.”

  • Class I — 2½″ outlets, for fire department use only.
  • Class II — 1½″ outlet with 1½″ hose, for occupant use.
  • Class III — 2½″ and 1½″ outlets (or 2½″ reduced with a removable reducer), for occupant and firefighter use.

A combined sprinkler/standpipe system incorporates the sprinkler water supply with a Class III standpipe; most new systems are built this way, and they generally require a fire pump to deliver adequate pressure at the upper levels. Engine companies should never use the unlined linen occupant hose — it is often old, poorly maintained, and may fail at fire department operating pressures. The one exception: a ladder or rescue company operating remotely from an engine company during searches, to save civilian or firefighter lives.

Expect standpipes in multifamily residential buildings over three floors, high-rise residential and office buildings, hospitals, terminals, warehouses, industrial buildings, enclosed malls, theaters, stadiums, parking garages, bridges, and tunnels. Risers are usually in enclosed stairwells but can be in public hallways or outside along fire escapes.

Engine Company Operations 2023 V-1, 6-1 to 6-4 and 6-16 — Standpipe Systems / Supplying Standpipe Systems

Who supplies the FDC — 2nd due pumps it, 3rd due relays

The first critical task facing the 2nd due Engine Company at a standpipe-equipped building is to establish a water supply by pumping into the FDC connections. The manual’s assignment:

“The second Engine Company arriving on the first alarm should take a position at the appropriate FDC standpipe connection and supply two 3″ lines into the FDC Siamese and connect to the nearest hydrant. The third arriving Engine Company should relay pump to the second engine company from the next nearest hydrant.”

The two engine companies work in series, not in parallel. This evolution — one engine, two 3″ lines into the building connection — is exactly the 2nd-due engineer’s job. The redundancy the manual requires (“two engine companies for each Siamese connection”) comes from the 3rd due relay-pumping into you from the next nearest hydrant, not from a second engine on the same Siamese. Larger buildings often have multiple FDC connections on different street fronts — later-arriving engines continue the procedure on those.

On wet standpipes the pumper augments the system so flow needs are met at adequate pressure; on dry standpipes the pumper is the supply.

Engine Company Operations 2023 V-1, 6-16 — Supplying Standpipe Systems · re-verified 2026-08-30

What the attack crews carry in

High-rise bundles — four 50′ lengths of 2½″ hose packed in a Denver load with straps; one bundle has the high-rise nozzle pre-attached. The manual requires 2½″ hose and smooth-bore nozzles off standpipes in commercial and residential low-rise and high-rise buildings, mainly because of the limited pressure in wet systems built before 1993 and the extinguishing capability of 2½″ hose. For residential occupancies and hotels, the 1¾″ Minuteman bundle can be attached to the high-rise shut-off, for overhaul and if fire conditions allow.

High-rise kit — a nylon bag with, at minimum: gate valve, spanner wrenches, door wedges, pipe wrench, pressure gauge, 30-degree elbow, and PRD/PRV adjustment tools.

  • 2½″ high-rise nozzle — a ball-style shut-off with a built-in 2½″-to-1½″ reducer taking the 1⅛″ smooth bore tip; the shut-off also lets the crew turn off the water and extend the stretch at the nozzle.
  • Gate valve — gives the firefighter at the outlet control over discharge pressure and redundancy if the outlet valve or PRD/PRV fails.
  • In-line pressure gauge — attached to the gate valve’s 2½″ outlet before the hose, so the company can dial in the correct pressure for the hose stretched.
  • Elbow — reduces bends or kinks at the outlet and eases hookup inside a hallway hose cabinet.

Engine Company Operations 2023 V-1, 6-5 to 6-8 — Standpipe Hose and Equipment / Operating from Standpipe Systems

Getting up the building — stairs, elevators, and the hookup floor

In low-rise buildings, fire attack crews do not use elevators — hose and equipment go up the stairs. Crews may use the elevators in buildings over six stories, provided that an Elevator Operator is in place and the crews exit the elevator a minimum of two floors below the fire floor.

Pick the hose outlet in the stairway closest to the fire to minimize the stretch. All primary standpipe hookups must be made on the floor below the fire. Additional hoselines may have to connect two floors below the fire or in more distant stairways — second- and third-line companies should anticipate this and add lengths to their stretch. Under no circumstances hook up at an outlet that does not protect the crew from heat and smoke, such as in a corridor or hallway.

Charging the line: in commercial buildings the line is always charged within the confines of the stairway. A bedroom or kitchen fire in a residential building may allow a dry stretch to the apartment door — but with a more developed fire, wind, or an open apartment door, the stairway is the only safe option. If any doubt exists, charge the line in the stairway.

Engine Company Operations 2023 V-1, 6-8 to 6-10 — Operating from Standpipe Systems

Four operations at the outlet valve before hose goes on
  • 1 — Make sure the hose outlet valve is closed before removing the outlet cap. On dry systems, outlet valves may sit open on other floors — firefighters must be assigned to shut them so they don’t rob pressure from the system.
  • 2 — Remove or adjust the pressure-regulating device if present. Some PRDs remove; non-removable ones must be adjusted fully open (adjustment tools are in the high-rise kit). A third type can neither be removed nor field-adjusted — the most dangerous kind, which should be identified during pre-fire planning and disseminated to all affected companies.
  • 3 — Flush the system through the open outlet valve. Garbage and debris collect in risers, and flushing keeps the nozzle from clogging — it also proves the outlet valve works.
  • 4 — Attach the gate valve and in-line gauge, then the hose, ready to charge on the officer’s orders. Pressure adjustments are made on the in-line gauge with the nozzle fully open and flowing.

Engine Company Operations 2023 V-1, 6-9 to 6-10 — Operating from Standpipe Systems

Pressure-regulating devices — what you may find on the outlet

Flow restricting devices (most commonly an orifice plate) restrict flow through a reduced opening sized to a specific pressure and rate. They do not reduce static pressure, so higher pressures appear at lower flows.

Pressure reducing valves (PRVs) limit downstream pressure at all flow rates — static and flowing — and are set for a specific pressure, usually not adjustable without special tools. They are often installed where risers feed the sprinklers on individual floors as well as on hose outlets. PRVs removed the old ~20-story-per-zone height limit that flow restrictors imposed.

The hazard the manual flags: departments have found PRVs not properly set for the required discharge pressure, leaving crews with inadequate or excessive hoseline pressures. Standards now require a test/drain riser next to PRV-equipped risers so settings can be checked during regular inspections.

Background on outlet pressures: before 1993, NFPA 14 required only 65 psi residual at the topmost outlet — adequate for 2½″ smooth-bore work but not for 1¾″ lines with fog nozzles. The present standard requires a minimum of 100 psi at the top outlet. Know which buildings in the district fall under the old standard, and remember these minimums assume a properly maintained, 100%-dependable system — “a scenario we must realize does not exist in many buildings.”

Engine Company Operations 2023 V-1, 6-4 and 6-13 to 6-15 — Standpipe Systems / Pressure Reducing Devices

Source. ADO-Pumper Task Book, Evolution 1.6 — September 2024 version. Task-book steps verbatim, in printed order, with the printed numbering. Manual material: OFD Engine Company Operations 2023 V-1, Chapter 6 (Standpipe Operations); the OFD Hydraulic Manual (PDP, friction loss, elevation and appliance loss); ADO Task #19 Basic Pump Skills-Changeover; and the OFD Quick Reference Guide (May 2024) — each cited per block. Elevation computed to the nozzle floor, nozzle pressure counted once, the rig-specific reading of PSI mode, and the relief-valve pre-set are per Engineer Jason Anderson’s 2026-08-29 and 2026-08-30 rulings; the merged muscle-memory steps come from his engine evolution, transcribed 2026-08-28.

Version: prototype · Last reviewed 2026-08-30 · Compiled by Engineer Jason Anderson

Sections