Engine OperationsEvolution 1.8

Official evolution · ADO-Pumper Task Book · September 2024

Evolution 1.8 — Participate in Pumping a Hydrant as the Attack Pumper

OBJECTIVE: Pump hand lines while being supplied by source pumper at a hydrant

Secure the rig — in the cab

1

Right foot on brake

2

Set parking brake

3

Shift transmission to neutral

Engage the pump — in the cab

4

Shift from road to pump (engage the pump shift control lever)

5

Pump engaged light is on

6

Shift transmission to Drive (D)

7

OK TO PUMP light is on and

7a

Speedometer registers about 15 mph

Orem rigs: Engine 34 only

Engine 34 Pump shift operations:

  1. Right foot on brake
  2. Neutral
  3. Park brake
  4. Engage "water pump" switch
  5. Green light indicator on
8

Emergency/warning lights are on

9

Change radio to correct channel

Printed setup 2 lives on this step: communications must be constant between the two engineers for the whole evolution.

10

Remove right foot from brake

11

Apparatus does not move

12

Exit cab after looking both directions

Get water moving — on tank water

+

CHOCK WHEELS

Orem's printed 1.8 sheet has no chock step — it needs adding. Other pumper evolutions carry “Set wheel chocks” as an out-of-cab step, and ADO Task #19 makes chocking part of Step 1: “Position the apparatus in a safe positon, and immobilize it by setting the parking brake and chocking the wheels.”

1

Begin flowing water as the engineer of the attack pumper from 1 attack line

The printed step stops there. The sequence that carries it out:

1a

OPEN TANK TO PUMP

muscle memory
1b

OPEN TANK FILL / RECIRCULATION

muscle memory
Where this sits in the changeover task

ADO Task #19 puts the same two valves in the same order before any external water arrives: Step 3 “Open the tank-to-pump valve (if necessary)”, then Step 7 “Open the circulator valve or partially open the tank fill valve.”

ADO Task #19 Basic Pump Skills-Changeover, Operating Procedure Steps 3 and 7

1c

SET PSI CONTROL MODE BUTTON

muscle memory
Why PSI mode here, and not RPM

ADO Task #19 Step 4: “Set the transfer valve to the series (to PSI or RMP) positon depending on application.” The application on this evolution is hand lines from the attack pumper, so the governor holds a pressure. The other rig — the one on the hydrant — is printed the other way in Evolution 1.7: “Fill supply line to attack pumper and set to 'RPM MODE'.”

ADO Task #19, Operating Procedure Step 4 · ADO-Pumper Task Book, Evolution 1.7 out-of-cab step 2

1d

Check lines are fully deployed

muscle memory
1e

CHARGE LINES

muscle memory
1f

CALCULATE PDP

muscle memory
1g

SET PDP

muscle memory
What the Engineer has to know to set it
“In order to establish and maintain proper pumping pressures, all Engineers must know how many hoselines, the size and length of the hoseline, the type of nozzles being used, and their flow.”

Engine Company Operations 2023 V-1, Ch.1 Firefighter Assignments (1-11)

Take the supply — the changeover

2

Establish connections from supply pumper

2a

CONNECT LDH SUPPLY

muscle memory

Printed setup 1 sets the minimum: water must flow through a minimum of 100' of supply hose, with the apparatus at least 100' apart.

2b

OPEN PRESSURE RELIEF VALVE

muscle memory
How the relief valve is pre-set before hydrant water arrives

Set the Discharge Relief Valve to about 150, rev up psi to 150 while gating down the handlines to make sure they stay at the set pdp for them. Then when hydrant water is introduced there isn't as much of a pressure spike and the discharge relief valve will catch any extra. After the hydrant is fully opened, throttle back down.

ADO Task #19 asks for the same control to be established before the transition — Step 6: “Set the relief valve or pressure governor.”

Engineer Jason Anderson's engine evolution, 2026-08-30 review · ADO Task #19, Operating Procedure Step 6

3

Call for water

On this evolution the call goes to the engineer of the supply pumper, who is on the hydrant behind you — not to a firefighter at the hydrant.

3a

SIGNAL FOR WATER

muscle memory
3b

CLOSE PRESSURE RELIEF VALVE

muscle memory
3c

OPEN SUPPLY INTAKE SLOWLY (MONITOR GAUGES)

muscle memory
The changeover, in the task's own words
“To begin the transition, the operator opens the intake valve from the supply line very slowly while observing the pressure on the intake and discharge gauges. Start opening intake valve and adjusting the discharge pressure until the intake is completely open. It may be necessary to adjust the engine throttle to get the desire discharge pressure.”

Before that, the air in the empty supply hose has to be purged:

“Air in the empty supply hose will cause problems if it enters the pump while the pump is supplying attack lines under pressure. To purge this air, open the bleeder valve on the gated intake line so that the air can escape as the supply line fills with water. When all the air has been forced from the line, close the bleeder valve. The water is now at the pump and ready for the transition.”

ADO Task #19 Basic Pump Skills-Changeover, opening narrative

3d

CLOSE TANK TO PUMP

muscle memory
Order matters — intake open first
“After the intake valve is opened, the tank-to-pump valve can be closed.”

ADO Task #19 Basic Pump Skills-Changeover, opening narrative; the same order appears in Operating Procedure Step 8

3e

*NOTE STATIC HYDRANT PRESSURE*

muscle memory

On the attack pumper you are not on the hydrant — you read it on the pump master intake gauge, as the pressure the supply pumper is delivering to you.

Why note it

USE 1ST DIGIT METHOD TO DETERMINE ADDITIONAL LIKE VOLUMES REMAINING.

The manual asks for the same reading and gives it the same job: Engineers “should also monitor the residual pressure of the pump master intake gauge to determine the capability of supplying additional volumes when available or as needed.” That is the number printed step 7 asks you to act on.

Engineer Jason Anderson's engine evolution — see Engine Evolution · Engine Company Operations 2023 V-1, Ch.1 (1-11)

4

Maintain Communications with supply pumper to ensure 20psi residual pressure

Why 20 psi

20 psi minimum protects from drawing a vacuum on the intake hose.

The Hydraulic Manual builds the same floor into every relay pump discharge pressure: “PDP accounts for 20 psi residual pressure for the next pumper in the relay.”

Engineer Jason Anderson's engine evolution — closing note · OFD Hydraulic Manual, Maximum volume relay pump pressure

5

Fill tank water

Same step as REFILL TANK on the muscle-memory sequence — the printed sheet and the card agree here.

Why the tank goes back to full, and how
“However, the (tank-fill) valve should be left partially open until the water tank has been refilled. Note: A full tank provides a limited reserve water supply in the event that the external water supply is lost unexpectedly.”
“As soon as an adequate supply of water is available, divert enough of it through the tank-fill line to replenish the supply in the tank.”

ADO Task #19 Basic Pump Skills-Changeover, opening narrative and Operating Procedure Step 8

More lines, then shutting down

6

Flow additional hand lines

Printed setup 1 requires a minimum of 2 attack lines flowing from the attack pumper; step 1 started you on one.

7

Request additional pressure, if needed, to maintain 20 psi minimum residual pressure

The other engineer's matching step

Evolution 1.7 gives the supply pumper the answering half of this: “Adjust pump pressure, if needed, to maintain 20 psi minimum residual pressure at the attack pumper”, and “Maintain communication between engineers when additional lines are being placed into service.”

ADO-Pumper Task Book, Evolution 1.7 out-of-cab steps 5 and 6

8

Shut down hand line and note the change in residual pressure at the attack pumper

What the Hydraulic Manual adds to a mid-operation shutdown

The printed step closes the line and reads the gauge. The Hydraulic Manual attaches a condition to the equivalent step in a relay:

“Maintain water flow during temporary shutdowns by using one or more discharges as waste or dump lines.”

It also states the attack pumper's standing job in the same place: “Attack Pumper - adjust PDP as needed making sure to dump excess pressure.”

Unresolved: Evolution 1.8 carries no dump-line provision. Flagged as a committee item against the task book — do not treat this drop-down as an authorised change to the printed sheet.

OFD Hydraulic Manual, Constant Pressure Relay, Step 8 sub-bullet and “Maximum volume relay pump pressure”

9

To end operations shut down all lines at attack pumper first then supply pumper last

The order is fixed, and both sheets print it the same way — you first, the hydrant rig last.

20

Maintain 20 PSI intake pressure.

20 psi minimum protects from drawing a vacuum on the intake hose. The printed sheet states the same floor twice from your seat: setup 3, and out-of-cab steps 4 and 7.

What the manual teaches about being the attack pumper

Which seat you are in — the three pumper roles
  • Water supply pumper — “Pumper that takes water from a hydrant or static source and pumps it under pressure to the next apparatus in the relay pumping operation. Water supply pumpers should be the apparatus with the largest pumping capacity. Some jurisdictions refer to water supply pumpers as source pumpers.” That is the other rig.
  • Relay pumper — receives water from the source pumper or another relay pumper, raises the pressure, and supplies the next apparatus. May be of smaller capacity, because it uses the acquired energy of previous pumpers in the relay.
  • Fire attack pumper — “Pumping apparatus located at the fire scene that receives water from the relay and is responsible for supplying the attack lines and appliances required for fire suppression.” That is your seat in this evolution.

The task book's own objective uses the manual's word for the rig feeding you — “being supplied by source pumper at a hydrant” — while its title and setup call the same rig the “supply pumper.” The Hydraulic Manual's “Key positions in a relay operation” names only Source Pumper, Relay Pumper/Pumpers and Attack Pumper.

Engine Company Operations 2023 V-1, p.110 (5-14) · OFD Hydraulic Manual, Key positions in a relay operation

Where this tactic ranks — high-flow hydrant operations

When more water is needed than a single supply line delivers, the manual ranks the options from least to best preferred:

  1. Multiple supply lines from a single hydrant (least preferred)
  2. Pumping the hydrant with the 2nd or 3rd due engine supplying the attack pumper — this evolution, from the receiving end
  3. Multiple supply lines from different hydrants sharing the same water main
  4. Multiple supply lines from different hydrants not sharing the same water main (best preferred)

Engine Company Operations 2023 V-1, p.109 (5-13)

The changeover you are performing — ADO Task #19, start to finish

Out-of-cab steps 1 through 5 on this sheet are a transition from tank water to an external supply. The task states the case exactly:

“Transition from the water tank to an external water supply source most commonly involves the use of a pressurized source. This will be a hose-line being supplied by another apparatus or from a fire hydrant.”

Its nine-step operating procedure, in order:

  1. Position the apparatus in a safe positon, and immobilize it by setting the parking brake and chocking the wheels.
  2. Engage the pump, and select the proper gear in the road transmission. Lock the gear into place.
  3. Open the tank-to-pump valve (if necessary).
  4. Set the transfer valve to the series (to PSI or RMP) positon depending on application.
  5. Increase the throttle setting to obtain the desired pressure, priming (if necessary).
  6. Set the relief valve or pressure governor.
  7. Open the circulator valve or partially open the tank fill valve.
  8. When an external supply becomes available, open the intake valve while closing the tank-to-pump valve (if necessary). As soon as an adequate supply of water is available, divert enough of it through the tank-fill line to replenish the supply in the tank.
  9. Adjust the engine throttle to achieve the desired discharge pressure (if necessary).

Step 1 is where the chock step on this page comes from.

ADO Task #19 Basic Pump Skills-Changeover, Operating Procedure for Transition to an External Water Supply, Steps 1–9

What the attack pumper does in a Constant Pressure Relay

Orem's documented multi-pumper method puts the variable pressure on your rig and holds everyone behind you steady:

  • Step 1: Position Attack Pumper — “Placed at a forward 'Key' attack position.”
  • Step 4: all pumpers except the source pumper open a discharge to exhaust air from the lines.
  • Step 5–6: source pumper throttles up to 175 psi; relay pumpers do the same.
  • Step 7: all Driver/Operators set their intake relief valves.
  • Step 8: “Attack pumper adjusts PDP to supply attack lines” — “Attack Pumper - adjust PDP as needed making sure to dump excess pressure.”
“Orem Fire Department uses the Constant Pressure Relay method for establishing hydraulic pressures and distances during relay operations.”

OFD Hydraulic Manual, Constant Pressure Relay (Limited Max Volume), Steps 1–8 and “Key positions in a relay operation” · Engine Company Operations 2023 V-1, p.111 (5-15)

When two rigs 100' apart become a relay
“Using two or more pumpers to move water over a long distance by operating them in series; water discharged from one pumper flows through hoses to the inlet of the next pumper, and so on. Also known as Relay Pumping.”
“A relay pumping operation consists of a pumper positioned at the water supply source that is used to pump water under pressure through one or more supply lines to another pumper connected further down the supply line(s). This pumper boosts the pressure to supply the next pumper and so on until water reaches the attack pumper. In order to be effective, relay operations require pre-planning, training, and coordinating of all participants.”

The drill on this sheet is that operation at its smallest — two rigs, no relay pumper in between. Add distance or a third pumper and the Hydraulic Manual spaces relay pumpers at 750-foot intervals.

Engine Company Operations 2023 V-1, p.110 (5-14) · OFD Hydraulic Manual, Implementing a constant pressure relay operation, Step 3

How much supply hose the flow needs

Printed setup 1 sets a floor of 100' of supply hose but says nothing about how many lines. The manual does:

“A single 5-inch line may not flow all of the available water from a hydrant and/or water main.”
“Provide one 5-inch hose line for every 1000 gpm to be delivered.”

Engine Company Operations 2023 V-1, p.101 (5-5), Basic Hydrant Flows

What the Engineer must know and watch throughout
“In order to establish and maintain proper pumping pressures, all Engineers must know how many hoselines, the size and length of the hoseline, the type of nozzles being used, and their flow. It is imperative that the Engineer listen closely to the radio at all times for traffic concerning charging, shutting down or adjusting hose line pressures on hose lines. They should also monitor the residual pressure of the pump master intake gauge to determine the capability of supplying additional volumes when available or as needed.”

That paragraph is the manual's version of printed steps 4, 6, 7 and 8 on this sheet — constant radio traffic with the other engineer, and the master intake gauge as the instrument that answers “can I add another line?”

Engine Company Operations 2023 V-1, Ch.1 Firefighter Assignments (1-11)

Who ends up as the attack pumper on the fireground

The manual assigns the supply, which decides who is being supplied:

“The first arriving Engine Company Officer will make the determination for the need for water supply or communicate that responsibility to the second arriving Engine Company. In either case that information is transmitted from the first arriving to the second arriving Engine Company.”
“The Engineer of the second arriving engine is assigned to supply the first engine, this should be accomplished without placing their apparatus at the front of the fire scene.”

Engine Company Operations 2023 V-1, Ch.1 (1-10 to 1-11)

The Quick Reference Guide names the same pairing by building type:

  • Residential & multi-family 1–3 floors, and Commercial — 2nd Engine Company: “Pump hydrant for 1st engine if needed” — so the 1st Engine is the attack pumper.
  • Mid rise, 4 floors and above — 3rd Engine Company: “Pump hydrant for 2nd engine.”
  • Mid rise and Commercial — 5th Engine Company: “Complete water supply, pump hydrant for 4th engine if needed.”

OFD Quick Reference Guide for Initial Company Operations, May 2024 — which states it “is a quick reference document and is not designed to override or replace understanding of the full applicable Manuals”

IF WATER IS LOST

Your supply is another engineer, not a hydrant. Get on the radio to the supply pumper first, and work your own pump while you wait.

The tank you refilled at step 5 is the reserve — “A full tank provides a limited reserve water supply in the event that the external water supply is lost unexpectedly.”

If the supply cavitates or pulls a vacuum — close the supply, then open tank to pump.

Emergency pump operations — the full drilled sequence

Sources. ADO-Pumper Task Book, Evolution 1.8 (September 2024 Version) — objective, setup and numbered steps verbatim, in printed order, with the printed numbering; the Engine 34 pump-shift sub-sequence appears where the sheet prints it. Merged + steps, the lettered sub-steps and the relief-valve pre-set per Engineer Jason Anderson's engine evolution card (transcribed 2026-08-28) and his 2026-08-30 review; the added chock step matches the master-sheet pattern. Manual material from Engine Company Operations 2023 V-1, Chapter 1 (Firefighter Assignments) and Chapter 5 (Water Supply), ADO Task #19 Basic Pump Skills-Changeover, the OFD Hydraulic Manual (Constant Pressure Relay), and the Quick Reference Guide for Initial Company Operations (May 2024) — cited per block.

Version: prototype · Last reviewed 2026-08-30 · Compiled by Engineer Jason Anderson

Sections